Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T09CM01836
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/02/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The Appeal to the Building Official must be signed by the appellant and the owner. The appeal, along with a receipt for the appeal fee, is to be submitted separately from the drawings. 2. What is the source of the code amendment attached to the appeal; it is not an amendment contained in any codes adopted by the City of Tucson. 3. A manning roughness factor of 0.009 is not suitable for sewer design. A value of 0.013 provides allowance for interior coatings (e.g. grease), flow disturbances due to rough joints or pipe misalignment and for future pipe condition. In addition, the submitted calculation has a result that is not supported by the input data. 4. Any calculations submitted with the appeal shall be sealed by an Arizona registrant. |
| 10/05/2009 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 10/07/2009 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 10/09/2009 | TERRY STEVENS | ZONING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/26/2009 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 10/26/2009 | SUE REEVES | REJECT SHELF | Completed |