Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL BLDG/WWM
Permit Number - T09CM01827
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/15/2009 | RONALD BROWN | BUILDING-RESIDENTIAL | REVIEW | Denied | Comment 4b: Provide additional vertical support where the new roofing ridge beam terminates on top of the existing roof. Comment 9a: A junctioon box in the ceiling will not comply with code, Section E33905.2. The junction box must be accessible. You may need to provide two junction boxes to pick up all the branch circuits serviced by the existing panel. Please note if the existing panel is to be relocated or you are providing a new panel. There are conflicting notes to that effect on the panel schedule and the electrical floor plan. Show all electrical conditions on the new riser diagram concerning the new junction box/es required to handel the existing branch circuits. END OF REVIEW |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/16/2009 | CPIERCE1 | OUT TO CUSTOMER | Completed |
| 09/16/2009 | CPIERCE1 | REJECT SHELF | Completed |