Permit Number: T09CM01827
Parcel: 121113110

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T09CM01827
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/15/2009 RONALD BROWN BUILDING-RESIDENTIAL REVIEW Denied Comment 4b: Provide additional vertical support where the new roofing ridge beam terminates on top of the existing roof.
Comment 9a: A junctioon box in the ceiling will not comply with code, Section E33905.2. The junction box must be accessible. You may need to provide two junction boxes to pick up all the branch circuits serviced by the existing panel.

Please note if the existing panel is to be relocated or you are providing a new panel. There are conflicting notes to that effect on the panel schedule and the electrical floor plan.

Show all electrical conditions on the new riser diagram concerning the new junction box/es required to handel the existing branch circuits.

END OF REVIEW

Final Status

Task End Date Reviewer's Name Type of Review Description
09/16/2009 CPIERCE1 OUT TO CUSTOMER Completed
09/16/2009 CPIERCE1 REJECT SHELF Completed