Permit Number: T09CM01819
Parcel: 13710512A

Address:
5660 S 12TH AV

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM01819
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/14/2009 GERRY KOZIOL WWM REVIEW Denied NEED 5TH FLOOR CREDIT EVALUATION
07/14/2009 DAVE MANN FIRE REVIEW Approved
07/17/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Given the temperature range of the water supply in Tucson (as high as 90.3 degrees Fahrenheit), specify how the temperature limit stop on the lavatory faucet is to be adjusted to guarantee a maximum delivery temperature of 110 degrees Fahrenheit. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006.
2. Provide pressure-absorbing devices for the water connections to fixtures equipped with quick-acting or solenoid valves. Reference: Section 609.10, UPC 2006.
3. Show how the water piping for restroom 117 has been modified. Show also, how the water supply pipes have been sized. Reference: Sections 103.2.3 and 610.0, UPC 2006.
07/17/2009 ROBERT SHERRY WATER REVIEW Approved
07/17/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide information on the sequence of operation for the restroom exhaust fans to show that recirculation of the air from the restrooms will not occur. Reference: Section 403.2.1, IMC 2006.
2. Provide information to show that adequate ventilation will be supplied to the kitchen. Reference: Section 403.3 and footnotes f and g, Table 403.3, IMC 2006.
3. Show that the clearances for the grease duct comply with Section 506.3.6, IMC 2006.
4. Show that the make up air duct within 18" of the Type I exhaust hood complies with the requirements of Section 506.3.1.2, IMC 2006.
5. Specify the mounting height of the grease exhaust fan. Reference: Section 506.3.12.3, IMC 2006.
6. Provide the specifications and size of the proposed Type I hood. Unless the proposed Type I kitchen hood has been factory-built and tested in accordance with UL 710, the minimum air flow rates shall conform to the requirements of Section 507.13, IMC 2006. Reference: Section 507.1, IMC 2006.
7. Provide structural calculations and details to show that the proposed Type I hood is supported from the building structure in accordance with Section 507.6, IMC 2006. Reference: Section 302.1, IMC 2006.
8. Show that the hood installation complies with Section 507.9, IMC 2006 for clearances. (i.e. provide information regarding the construction of the wall adjacent to the grease hood.)
9. Provide information to show that the operation of the Type I hood and the hood exhaust fan complies with Section 507.2.1.1, IMC 2006.
10. Show how water service and drain piping is to be installed for the make up air unit; it is not shown on the plumbing drawings. Reference: Section 106.3.1, IMC.
07/20/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/28/2009 CPIERCE1 OUT TO CUSTOMER Completed
07/28/2009 SUE REEVES REJECT SHELF Completed