Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T09CM01789
Parcel: 126160880

Address:
129 S IRVING AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T09CM01789
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/11/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved