Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T09CM01784
Parcel: 12509021B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM01784
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/08/2009 MICHAEL ST. PAUL ZONING REVIEW Approved
07/08/2009 BIANCA RAMIREZ ENGINEERING REVIEW Approved
07/08/2009 RONALD BROWN ZONING HC SITE REVIEW Denied SECOND TOILET NOT COMPLIANT WITH ACCESSIBLE CODE DUE TO SPACE REQUIREMENTS.
07/08/2009 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
07/08/2009 RONALD BROWN ADA REVIEW Passed
07/09/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show the R-value for the ductwork (R-8 outside, R-4.2 in semi-conditioned spaces).
2. Indicate the amount of outside air to be delivered by each rooftop unit.
3. The hallway may not be used as a return duct. reference: Section 601.2, IMC 2006.
4. Provide the operating schedule for the restroom exhaust fan; complete recirculation of the air supplied to the restroom is prohibited. Reference Section 403.2.1 (3), IMC 2006.
5. Clarify how Section 603.14 applies to this activity.
6. Indicate how the supply air is to be balanced (e.g. volume dampers). Reference: Section 603.17, IMC 2006.
07/09/2009 DAVE MANN FIRE REVIEW Approved
07/09/2009 ROBERT SHERRY WATER REVIEW Approved
07/09/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Need correct plans, Ray T Majuta, 7/09/09
07/09/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show the route and termination point of the T&P relief pipe for the water heater.
2. Show how the water temperature to the lavatory will be limited to 110 degrees Fahrenheit or less.
3. Correct the water conservation notes to comply with ARS Title 45, Chapter 1, Article 12.
4. Provide the minimum plumbing facilities for this occupancy, i.e. a drinking fountain or permanently-connected water dispenser.
07/10/2009 THAUSER1 WWM REVIEW Needs Review
07/10/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review