Permit Number: T09CM01702
Parcel: 12620001C

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T09CM01702
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/10/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Comment not resolved. Provide sufficient detail on the drawings (or specifications) to evaluate the energy compliance of the building envelope. No information has been included regarding the U-factor, SHGF, or window/entry door construction to back up the energy calculations. Reference: Sections 101.4 and 104.2, International Energy Conservation Code 2006.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/11/2009 CPIERCE1 OUT TO CUSTOMER Completed
08/11/2009 SUE REEVES REJECT SHELF Completed