Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T09CM01702
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/10/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Comment not resolved. Provide sufficient detail on the drawings (or specifications) to evaluate the energy compliance of the building envelope. No information has been included regarding the U-factor, SHGF, or window/entry door construction to back up the energy calculations. Reference: Sections 101.4 and 104.2, International Energy Conservation Code 2006. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/11/2009 | CPIERCE1 | OUT TO CUSTOMER | Completed |
| 08/11/2009 | SUE REEVES | REJECT SHELF | Completed |