Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T09CM01702
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/07/2009 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | COT OWNED/OPERATED PROPERTY |
| 07/07/2009 | RONALD BROWN | ADA | REVIEW | Passed | |
| 07/07/2009 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 07/09/2009 | DAVE MANN | FIRE | REVIEW | Approved | |
| 07/15/2009 | GERRY KOZIOL | WWM | REVIEW | Passed | |
| 07/20/2009 | RICK MYERS | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 07/20/2009 | SREEVES1 | WATER | REVIEW | Approved | |
| 07/21/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide energy code compliance calculations. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation. Reference: Sections 101.4 and 104.2, International Energy Conservation Code 2006. 2. Provide calculations demonstrating adequate ventilation. Reference: Section 403.1, IMC 2006. |
| 07/27/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |