Permit Number: T09CM01702
Parcel: 12620001C

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T09CM01702
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/07/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed COT OWNED/OPERATED PROPERTY
07/07/2009 RONALD BROWN ADA REVIEW Passed
07/07/2009 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
07/09/2009 DAVE MANN FIRE REVIEW Approved
07/15/2009 GERRY KOZIOL WWM REVIEW Passed
07/20/2009 RICK MYERS PLUMBING-COMMERCIAL REVIEW Approved
07/20/2009 SREEVES1 WATER REVIEW Approved
07/21/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide energy code compliance calculations. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation. Reference: Sections 101.4 and 104.2, International Energy Conservation Code 2006.
2. Provide calculations demonstrating adequate ventilation. Reference: Section 403.1, IMC 2006.
07/27/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved