Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T09CM01699
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/12/2009 | ERIC NEWCOMB | ZONING HC SITE | REVIEW | Approved | |
08/12/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
08/19/2009 | RICK MYERS | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Show the location and the size of the backflow device for the water at the air/water/vacuum station. If the units have a built in backflow device, provide a detail of the unit showing how protection is provided. 2. Clarify how the perimeter gutter is connected, and piped tio the column drains. Reference: 103.2.3 2006 UPC. |
08/26/2009 | LAITH ALSHAMI | ENGINEERING | REVIEW | Denied | Laith Alshami, Engineering and Floodplain Review, 08/26/2009, The Site Plan can not be approved until the development package has been approved. |
09/04/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |