Permit Number: T09CM01667
Parcel: 12612244E

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM01667
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/07/2009 MICHAEL ST. PAUL ZONING REVIEW Approved
07/14/2009 JIM MILITELLO MECHANICAL-COMMERCIAL REVIEW Needs Review
07/14/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Needs Review
07/14/2009 JMILITE1 WATER REVIEW Approved
07/14/2009 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. provide structural calulations for all roof top mechanical units.
07/14/2009 JIM MILITELLO PLUMBING-COMMERCIAL REVIEW Needs Review
07/14/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/14/2009 RONALD BROWN ZONING HC SITE REVIEW Denied 1. provide proper ewc clearance as per section 602.
2. demo plan shows to remove rr 1 and 2 toilet fixtures and architectural plan shows to remain. please verify.
3. at boys and girls gang toilets, provide 42 inch clearance to accessible toilet stall. plan shows 38 inches.
4. verify accessibility of existing urinal to remain.
5. verify clearances at lavatory at boys and girls #2 toilets.
6. doors #4 and 5 provide 18 inch strike clearance.
7. provide large scale toilet floor plan and interior elevations showing all accessability accessories and critical dimenions.
8. clarify 2 hour seperation wall on floor plan.
9. correct toilet signage location as per section 703.311
end of review.
07/14/2009 RONALD BROWN ADA REVIEW Passed
07/16/2009 CAGUILA1 WWM REVIEW Needs Review
07/16/2009 CAGUILA1 FIRE REVIEW Needs Review
07/16/2009 CAGUILA1 ENGINEERING REVIEW Needs Review