Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T09CM01665
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/30/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 06/30/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 06/30/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project:T09CM01665 1915 E ST Electrical plans rejected for following; 1.Show service entrance conductor sizr. 2. Show 2 ground rods. 3. Indicate on plan service to remain 200amp only to be upgraded. 4. All emergency lights to be tied to same circuit as area. 5. Clarify lumen count and specify correct wattage for fixtures. 6. Correct circuit for new AC. 7. Circuit B-1 load to be corrected. RT Majuta DSD City of Tucson 6/30/09 520/837/4988 |
| 06/30/2009 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 06/30/2009 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 06/30/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 06/30/2009 | ERIC NEWCOMB | ZONING HC SITE | REVIEW | Approved | |
| 06/30/2009 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 07/01/2009 | CPIERCE1 | WWM | REVIEW | Needs Review | |
| 07/01/2009 | CPIERCE1 | ZONING | REVIEW | Needs Review | |
| 07/01/2009 | CPIERCE1 | ENGINEERING | REVIEW | Needs Review | |
| 07/01/2009 | MARTIN BROWN | FIRE | REVIEW | Approved |