Permit Number: T09CM01634
Parcel: 120063210

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T09CM01634
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/01/2009 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Please provide a completed 8 1/2" x 11" Code Review Check List Analysis Data form as provide in the Permit Review Forms and Information of our web site.
2. A detailed sprial stair drawing is included in the drawing submittal. Why does it have to be a deferred submittal?
3. Please provide a letter to LeeRay Hanley stating that the roof trusses are to be a deferred submittal.
4. Please include with the deferred truss submittals, complete structural details and calculations for all roof top mounted HVAC units.
5. Please provide completed special inspection forms for the inspections outlined in the structural specifications.

END OF REVIEW
07/01/2009 RONALD BROWN ZONING HC SITE REVIEW Denied 1. Accessible toilet signage must comply with ICC/ANSI 117.1, Section 703.3.11 Location.
07/02/2009 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed Impact Fee's Do Apply; West District; 2,896 Square Foot Retail Bldg; Demolition Permit T07BU01762 will credit permit with 2,919 Square Feet; 23 Square feet of credit is remaining on T07BU01762. An administrative fee of $50 is remaining.
07/07/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: 4301 S 6TH Av
New Retail Bldg, 101,019,117,125
T09CM01634

The Electrical Plans for this project have been denied for the following:

1. Per City of Tucson Submittal Requirements, provide 2006 IECC Lighting Calculations for interior.
2. Per City of Tucson Submittal Requirements, provide Outdoor Lighting compliance per The City of Tucson Outdoor Lighting Code.
3. The units have been assigned numbers, 101,109,117,125. Please re-number the individual panels according to new numbers.

Ray T Majuta
Electrical Plan Ck
PSD<City of Tucson,
7/08/09
Ray.Majuta@tucsonaz.gov.
520-837/4988
07/10/2009 STEVE SHIELDS ZONING REVIEW Approved
07/13/2009 GERRY KOZIOL WWM REVIEW Approved
07/16/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide energy code compliance calculations for this building. Reference: Section 101.4, International Energy Conservation Code 2006
2. Provide the U-value for the windows and glazed doors to be used for this building. Reference: Section 104.2 IECC 2006.
3. Provide structural calculations to verify that the existing roof is capable of supporting the additional dead load due to the installation of the roof top units. Reference: Section 302.1, IMC 2006.
4. Show how adequate access is being provided for the equipment located on the roof. Reference: Section 306.5, IMC 2006.
5. Revise the size of the condensate drains in accordance with Section 307.2.1, IMC 2006, as amended by the City of Tucson.
6. Correct the balancing data for the south rooftop A/C unit. It is scheduled for 1200 CFM but according to the mechanical plans, delivers only 1175 CFM. Reference: Section 106.3.1, IMC 2006.
7. Clarify the outside air calculations; the area of the spaces considered in the calculations shall equal the spaces shown on the drawings. In addition, show that the common ventilation system is sized in accordance with Section 403.3.2, IMC 2006.
8. Provide information on the sequence of operation for the restroom exhaust fans to show that recirculation of the air from the restrooms will not occur. Reference: Section 403.2.1, IMC 2006.
9. Provide filters for the rooftop A/C units. Reference: Section 605.1, IMC 2006.
10. Provide the specifications for the A/C units as noted in the A/C unit schedule. Reference: Section 106.3.1, IMC 2006.
07/20/2009 RMYERS1 WATER REVIEW Denied 1. Plan shows 11/2" RPPBP and 11/2" yardwater piping to building. Waterline Sizing Calculations show a 1" RPPBP. 2. Reconfigure water calculation to include flush valves.
07/20/2009 RICK MYERS PLUMBING-COMMERCIAL REVIEW Denied 1. See sheet MP-01 Plumbing Plan: a. A two-way cleanout fitting may be installed where the building drain connects to the building sewer. All other locations require a directional cleanout. Reference section 707.4 exception #4 and 707.6 2006 UPC. 2. Sheet MP-01 detail "B": a. At water closet: Where a vent connects to a horizontal drain it shall have its invert taken off above the drainage centerline, downstream of the trap being served. Note: If you use an upper terminal cleanout, it shall be full size. 3. Sheet MP-01 detail "B" At floor drain: Horizontal venting below the flood rim shall be limited to structural conditions. A partition within the trap arm distance allows the floor drain to be vented coventionally. Reference 905.2 and 905.3 2006 UPC: Vent Pipe Grades and Connections. 4. Sheet MP-01 Plumbing Plan. Show how the floor is to be sloped to the drains. Reference 411.4 2006 UPC. 5. Show the cleanouts on the isometric drawings for the drinking fountains. Any branch over five feet in length from the main requires cleanouts. Reference 707.4 exception one 2006 UPC. Label all of the cleanouts with the correct size. 6. Sheet MP-01 Fixture Unit Schedule: Reference table 7-3 2006 UPC. Water closet flush valves discharge 6 DFUs. Also revise the plumbing water isometric: The plan shows 1/2" water being distributed to the flush valves. 7. Revise the Fixture Unit Schedule: Drinking Fountains on Table 7-3 2006 UPC equal .5 DFUs (per head) 8. With two DFUs added for the extra drinking fountain heads, and eight DFUs added to the water closets, the total DFUs equal fifty-two. 9. Provide Plumbing Notes. They are to include piping material types, the method of sterilization, and any 2006 IECC requirements for pipe insulation. 10. Include the type of water heater in the Plumbing Fixture Schedule. If a temperature and pressure relief valve is required, where is it to be drained? 11. Required Roof Drains. Show how the scuppers are to be installed on a flat roof. Show size and locations of gutters.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/23/2009 CINDY AGUILAR OUT TO CUSTOMER Completed
07/23/2009 SUE REEVES REJECT SHELF Completed