Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T09CM01624
Parcel: 125011260

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T09CM01624
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/05/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide information to show how the fan coils and the condensing units are mounted to the building structure and that they don't overstress the structure. Resolve the type of mounting to be used for the condensing units.
2. Show the location of the specified exhaust fan on the mechanical floor plan.
10/05/2009 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied Please proviide structural caluculations for the fan coil unit mounting and the two roof top mounted units. Please coordinate RTP unit mounting details between arch,struct, and mechanical.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/14/2009 CINDY AGUILAR APPROVAL SHELF Completed
10/14/2009 CINDY AGUILAR OUT TO CUSTOMER Completed