Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T09CM01624
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/05/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide information to show how the fan coils and the condensing units are mounted to the building structure and that they don't overstress the structure. Resolve the type of mounting to be used for the condensing units. 2. Show the location of the specified exhaust fan on the mechanical floor plan. |
10/05/2009 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | Please proviide structural caluculations for the fan coil unit mounting and the two roof top mounted units. Please coordinate RTP unit mounting details between arch,struct, and mechanical. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
10/14/2009 | CINDY AGUILAR | APPROVAL SHELF | Completed |
10/14/2009 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |