Permit Number: T09CM01624
Parcel: 125011260

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T09CM01624
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/10/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. A permanently legible imprint of the registrant's seal and signature, along with the date the documents were sealed, shall appear on either the cover, title, index page, or first sheet of each set of project specifications. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. (Sheets M-1, M-2, and C-1)
2. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that a notation shall be placed beneath the seal, either written, typed, or electronically generated, that provides the day, month, and year of the expiration of current registration. (Effective March 8, 2008). (All sheets)
3. Revise the font size used on the drawings to a minimum of 3/32-inch. Reference: Section 106.1.1, IBC 2006.