Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T09CM01624
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/10/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. A permanently legible imprint of the registrant's seal and signature, along with the date the documents were sealed, shall appear on either the cover, title, index page, or first sheet of each set of project specifications. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. (Sheets M-1, M-2, and C-1) 2. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that a notation shall be placed beneath the seal, either written, typed, or electronically generated, that provides the day, month, and year of the expiration of current registration. (Effective March 8, 2008). (All sheets) 3. Revise the font size used on the drawings to a minimum of 3/32-inch. Reference: Section 106.1.1, IBC 2006. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/17/2009 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 08/17/2009 | SUE REEVES | REJECT SHELF | Completed |