Permit Number: T09CM01624
Parcel: 125011260

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T09CM01624
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/22/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. The 2006 International Mechanical Code with Local Amendments is the relevant code for this project.
2. Detail B/M-1 calls for a smoke detector to be installed in the supply plenum of each A/C unit. The UMC section referenced is not appropriate to this jurisdiction. Reference: Section 606, IMC 2006.
3. The equipment room shown on sheet M-1 is significantly larger than the room dimensioned in the architectural drawings. Confirm the size of the room. Reference: Sections 106.3.1 and 502.4, IMC 2006.
4. Keynotes 8 and 9 on sheet A-1.1 refer to a ceiling-mounted exhaust fan for the equipment room (shown located over the battery rack on the reflected ceiling plan). Is the exhaust fan a part of this activity? Reference: Section 106.3.1, IMC 2006.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/27/2009 GERARDO BONILLA APPROVAL SHELF Completed
07/27/2009 GERARDO BONILLA OUT TO CUSTOMER Completed
07/27/2009 GERARDO BONILLA REJECT SHELF Completed