Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/22/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. The 2006 International Mechanical Code with Local Amendments is the relevant code for this project. 2. Detail B/M-1 calls for a smoke detector to be installed in the supply plenum of each A/C unit. The UMC section referenced is not appropriate to this jurisdiction. Reference: Section 606, IMC 2006. 3. The equipment room shown on sheet M-1 is significantly larger than the room dimensioned in the architectural drawings. Confirm the size of the room. Reference: Sections 106.3.1 and 502.4, IMC 2006. 4. Keynotes 8 and 9 on sheet A-1.1 refer to a ceiling-mounted exhaust fan for the equipment room (shown located over the battery rack on the reflected ceiling plan). Is the exhaust fan a part of this activity? Reference: Section 106.3.1, IMC 2006. |