Review Status: Completed
Review Details: REVISION - - 3RD
Permit Number - T09CM01621
Review Name: REVISION - - 3RD
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/06/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide a cleanout for the drain downstream of the grease interceptor. 2. Revise the design of the 3-compartment sink drainage to include an indirect waste for the sanitizing compartment, and a vent for the trap serving the wash and rinse compartments. 3. Provide an indirect waste receptor and a floor sink for the scullery area. |