Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T09CM01621
Parcel: 12404102B

Review Status: Completed

Review Details: REVISION - - 3RD

Permit Number - T09CM01621
Review Name: REVISION - - 3RD
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/06/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a cleanout for the drain downstream of the grease interceptor.
2. Revise the design of the 3-compartment sink drainage to include an indirect waste for the sanitizing compartment, and a vent for the trap serving the wash and rinse compartments.
3. Provide an indirect waste receptor and a floor sink for the scullery area.