Permit Number: T09CM01574
Parcel: 107030710

Address:
1934 W SPRING ST

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T09CM01574
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/08/2010 GERRY KOZIOL WWM REVIEW Approved
01/26/2010 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 1-28-10
Activity: T09CM01574
Address: 1934 W Spring St
Applicant: Chris Lespron

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Provide two copies of the corrected set of drawings (no clouds or revision numbers please) along with a set of the first submission (cloud corrections on this set please). All corrections and revisions shall be made on original tracings or finished reproducible set. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.
2. Any architect and/or engineer involved in the design of the structure shall seal the related sheets of plans including revisions, details and calculations in accordance with the rules of the State Board of Technical Registration.
3. As of 6/12/2007 the City of Tucson has adopted the 2006 IRC. All plan pages should reference this code. Appeal to the Building Official for use of the 2000 IRC or the 2003 IPC.

SITE PLAN:
4. Specify the location of all utility lines and service meters, R106.1.1.

FLOOR PLAN:
5. Specify use of existing rooms adjoining the proposed addition. Note: removing existing windows from sleeping rooms may require a new emergency escape rescue opening, R310.
6. Doors between a garage and a residence shall be self-closing minimum 20-minute fire-rated, R309.1 as amended.
7. Wall panel width must be at least 2'8" for alternate braced wall panels (garage) unless portal frame design is utilized, R602.10.6.

FOUNDATION PLAN:
8. Provide a note for termite treatment, R320 as amended.
9. Specify foundation hold-downs for alternate brace wall panels that have minimum uplift capacity of 1800 lbs (PAHD42 insufficient), R602.10.6.
10. Clarify all holdown references (appears to refer to keynotes).

SECTIONS - DETAILS:
11. Clarify attic ventilation details. Vented frieze boards with ceiling insulation tight to roof deck?
12. Specify the manufacturer of asphalt shingles consistent with unvented attic assembly.

PLUMBING PLAN:
13. Specify the diameter of the new water line from the meter to the building, P2903.7.
14. Water conservation requirements: Water closets = 1.6 gallons per flush, Sinks = 2.2 gpm, Showerheads = 2.5 gpm, P2903.2.
15. Shower and tub/shower combinations that have individual control valves shall be of the pressure balance or thermostatic mixing valve type.
16. Provide note requiring that water hammer arrestor be installed in accordance with ASSE 1010-2004 on water lines serving appliances equipped with quick-closing valves to include but not limited to: clothes washers, dishwashers, and refrigerators, IRC P2903.5.
17. Provide pressure and temperature relief valve for the water heater terminating to the exterior facing no more than 6 above the floor, P2803.6.1.

MECHANICAL PLAN:
18. Show the condensate line and secondary for HVAC unit, M1411.3.
19. Show dryer vent size and location for venting to exterior (max 25' w/bend reductions), M1502.2, M1502.6.
20. Gas appliances shall comply with Chapter 17, 2006 IRC. Show compliance for all appliances. Confined spaces require a minimum of two 100 SQ. IN. openings or provide appliance specifications for alternate design, M1702.2.
21. Provide make up air/combustion air for gas fired dryer, M1702.2.

ELECTRICAL PLAN:
22. Show bedroom outlets protected with a combination-type arc-fault breaker (receptacles, lights, and smoke detectors) on panel schedule, E3802.12.
23. Provide a complete panel schedule to include all wiring sizes, E3304.11, E3606.2.
24. Specify circuit designation for outlets located in the proposed sitting room, E3603.5.

OUTDOOR LIGHTING CODE
25. Provide an accurate lighting calculation in accordance with OLC 3.1.2. Unshielded lumen limit is subtracted from the total lumen allowance.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review