06/17/2009 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/30/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied PROJECT; T09CM01538
2550 W Sweetwater RD
120 KW PHOTOVOLTAIC SYSTEM


The electrical plans have been denied for the following,
1. NEC 2005 230-82 allows the photovoltaic system to be tied to the primary of a system, however it must be at the supply side of the service disconnect means. The CT cabinet you show being tied to will be locked out by the utility company rendering the connection not accessible.


Ray T Majuta
DSD City of Tucson
Elect Plan Ck
6/30/09