| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/17/2009 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 06/30/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | PROJECT; T09CM01538 2550 W Sweetwater RD 120 KW PHOTOVOLTAIC SYSTEM The electrical plans have been denied for the following, 1. NEC 2005 230-82 allows the photovoltaic system to be tied to the primary of a system, however it must be at the supply side of the service disconnect means. The CT cabinet you show being tied to will be locked out by the utility company rendering the connection not accessible. Ray T Majuta DSD City of Tucson Elect Plan Ck 6/30/09 Ray.Majuta@tucsonaz.gov |