Permit Number: T09CM01514
Parcel: 141114100

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM01514
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/15/2009 DAVE MANN FIRE REVIEW Approved
06/15/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
06/15/2009 RICK HOLLANDER ELECTRICAL-COMMERCIAL REVIEW Approved
06/15/2009 ROBERT SHERRY WATER REVIEW Approved
06/15/2009 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. NEED STRUCTURAL DETAILS AND CALCULATION FOR CANOPY ATTACHMENT
2. PROVIDE CANOPYY CUT SHEETS
06/15/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Directly connect the dog wash sinks (with traps and vents). Reference: Chapter 8, UPC 2006.
2. Provide specfication for the water heater.
3. Show how the hot water is to be tempered.
4. Provide a thermal expansion tank. Reference: Section 608.3, UPC 2006.
06/15/2009 RONALD BROWN ZONING HC SITE REVIEW Approved
06/15/2009 RONALD BROWN ADA REVIEW Passed NOT A COT OWNED/OPERATED PROPERTY
06/16/2009 GBONILL1 WWM REVIEW Needs Review
06/16/2009 GBONILL1 ZONING REVIEW Needs Review
06/16/2009 GBONILL1 ENGINEERING REVIEW Needs Review
06/16/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review