Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T09CM01513
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/08/2009 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
07/08/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
07/10/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
07/10/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | 1. The fixture connection sizes called out for the flush valves will result in water velocities greater than 8 FPS. Limit the water velocity to less than 8 FPS if copper piping is to be used. Reference: Section A 6.1, UPC 2006 and IS 3-2003, Section 2.6. 2. Show the sizes of the domestic water pipes on the riser diagram. Reference: Section 610.1, UPC 2006. 3. Show the required size of the tempering valve and how it is to be connected to the existing hot water supply. Reference: Section 103.2.3, UPC 2006. 4. Clarify the size of the drain line in the restroom from the floor cleanout to the connection to the new 4" drain line. 5. Show how the water and drain piping for the existing janitor's sink relates to the new water and drain piping. Reference: Section 103.2.3, UPC 2006. 6. Clarify that the restroom floors slope to the floor drains. Reference: Section 411.2, UPC 2006. |