Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T09CM01513
Parcel: 10512024E

Address:
4070 N ORACLE RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T09CM01513
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/08/2009 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/08/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
07/10/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
07/10/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved 1. The fixture connection sizes called out for the flush valves will result in water velocities greater than 8 FPS. Limit the water velocity to less than 8 FPS if copper piping is to be used. Reference: Section A 6.1, UPC 2006 and IS 3-2003, Section 2.6.
2. Show the sizes of the domestic water pipes on the riser diagram. Reference: Section 610.1, UPC 2006.
3. Show the required size of the tempering valve and how it is to be connected to the existing hot water supply.
Reference: Section 103.2.3, UPC 2006.
4. Clarify the size of the drain line in the restroom from the floor cleanout to the connection to the new 4" drain line.
5. Show how the water and drain piping for the existing janitor's sink relates to the new water and drain piping. Reference: Section 103.2.3, UPC 2006.
6. Clarify that the restroom floors slope to the floor drains. Reference: Section 411.2, UPC 2006.