Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T09CM01513
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/15/2009 | DAVE MANN | FIRE | REVIEW | Approved | |
06/17/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Complete recirculation of ventilation air from toilet rooms is prohibited. Reference: Section 403.2.1 (3), IMC 2006. |
06/17/2009 | RICK HOLLANDER | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project: T09CM01513 4070 N. Oracle Rd TI Need more information regarding existing circuits, and key notes 1 & 3 Rick Hollander DSD Electrical Plan Check 6/17/2009, 520-837-1088 |
06/17/2009 | ROBERT SHERRY | WATER | REVIEW | Approved | |
06/17/2009 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
06/17/2009 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
06/17/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Specify the materials to be used for the waste, vent, and water piping and fittings. Reference: Sections 604.0 and 701, UPC 2006. 2. The fixture connection sizes called out for the flush valves will result in water velocities greater than 8 FPS. Limit the water velocity to less than 8 FPS if copper piping is to be used. Reference: Section A 6.1, UPC 2006 and IS 3-2003, Section 2.6. 3. Provide pressure-absorbing devices for the water connections to appliances equipped with quick-acting or solenoid valves. Reference: Section 609.10, UPC 2006. 4. Provide water pressure and water pipe sizing calculations. Show the sizes of the pipes on the riser diagram. Reference: Section 610.1, UPC 2006. 5. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006. |
06/17/2009 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
06/17/2009 | RONALD BROWN | ZONING HC SITE | REVIEW | Approved | |
06/17/2009 | RONALD BROWN | ADA | REVIEW | Passed | NOT A COT OWNED/OPERATED PROPERTY |
07/08/2009 | GERRY KOZIOL | WWM | REVIEW | Approved | |
07/08/2009 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
07/08/2009 | DELMA ROBEY | OUT TO CUSTOMER | Completed |