Review Date Reviewer's Name Type of Review Description Status Comments
06/15/2009 DAVE MANN FIRE REVIEW Approved
06/17/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Complete recirculation of ventilation air from toilet rooms is prohibited. Reference: Section 403.2.1 (3), IMC 2006.
06/17/2009 RICK HOLLANDER ELECTRICAL-COMMERCIAL REVIEW Denied Project: T09CM01513
4070 N. Oracle Rd
TI



Need more information regarding existing circuits, and key notes 1 & 3


Rick Hollander
DSD Electrical Plan Check
6/17/2009, 520-837-1088
06/17/2009 ROBERT SHERRY WATER REVIEW Approved
06/17/2009 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
06/17/2009 JASON GREEN ENGINEERING REVIEW Approved
06/17/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Specify the materials to be used for the waste, vent, and water piping and fittings. Reference: Sections 604.0 and 701, UPC 2006.
2. The fixture connection sizes called out for the flush valves will result in water velocities greater than 8 FPS. Limit the water velocity to less than 8 FPS if copper piping is to be used. Reference: Section A 6.1, UPC 2006 and IS 3-2003, Section 2.6.
3. Provide pressure-absorbing devices for the water connections to appliances equipped with quick-acting or solenoid valves. Reference: Section 609.10, UPC 2006.
4. Provide water pressure and water pipe sizing calculations. Show the sizes of the pipes on the riser diagram. Reference: Section 610.1, UPC 2006.
5. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006.
06/17/2009 MICHAEL ST. PAUL ZONING REVIEW Approved
06/17/2009 RONALD BROWN ZONING HC SITE REVIEW Approved
06/17/2009 RONALD BROWN ADA REVIEW Passed NOT A COT OWNED/OPERATED PROPERTY
07/08/2009 GERRY KOZIOL WWM REVIEW Approved
07/08/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
07/08/2009 DELMA ROBEY OUT TO CUSTOMER Completed