07/06/2009 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS T09CM01479

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2006 International Energy Conservation Code, and Arizona State amendments to the 2006 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
All corrections and revisions shall be made on original tracings or a finished reproducible set. Return two sets along with a set of the first submission for reference. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets. (Do not cloud the changes made for comment revisions). Incorporate changes on originals and provide two copied sets for review.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

The City of Tucson adopted the 2006 IRC with amendments on 6/12/2007, the 2006 UPC with amendments on 7/10/2007, effective 1/1/2007 the Inclusive Home Design and starting 3/1/2009 Solar Water Preparation. All plans should reference these codes. Adopted amendments are found at: http://www.tucsonaz.gov/dsd/Codes___Ordinances/Building_Codes/building_codes.html

GENERAL NOTES:

" Interior alterations require the installation of smoke alarms at existing bedrooms, R313.2.1.

SECTIONS - DETAILS:

1. Show the ceiling gypsum board as either 5/8" or ½" sag resistant when applied to 24" o/c ceiling framing, IRC table R702.3.5 footnote d.

MECHANICAL PLANS:

1. Show the proposed supply duct is located in a chase within the building thermal envelope, allowing insulation rating less than R-8, IECC 503.2.7 (City of Tucson Amended).

ELECTRICAL PLANS:

1. Provide a location for sub-panel 'B' with a clear working space of 30"wide x 36"deep from floor to ceiling, E3305.2.
2. Revise the electrical load calculation for sub-panel 'B' showing 8,606/240=35.9A, E3502.2.
3. Show at least one wall switch controlled light at the exterior door, E3803.3. This light may be noted as an existing fixture in the immediate area.