Permit Number - T09CM01469
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/08/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 07/08/2009 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 07/28/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project: T09CM01469 7333 E 22nd St Church TI The Electrical Plans have been denied for the following; 1. Sheet E-3 , AC-4 feeding from SES under a 150 amp CB shows 3 #2' s and a #6 grd. The unit draws 116 amps and thr NEC table for ampacities shows 115 amps allowed under the 75' C column ? 2. Sheet E-5 at Panel Schedule LA, what does "delete" mean ? EF-3 is still on the power plan. Ray T Majuta PDS City of Tucson Elect Plan Ck 7/28/09 520-837-4988 Ray.Majuta@tucsonaz.gov |