Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T09CM01469
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/09/2009 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 06/09/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show how the exhaust fan is being connected to the building structure and provide calculations to show that the building structure is not being adversely affected. Reference: Section 302.1, IMC 2006. 2. Resolve the conflict between the note calling for R-6 duct insulation outside and the R-8 insulation called for in detail 101. The minimum insulation for ducts located outside of the building envelope or in a space that freely communicates with the outside is R-8. Reference: Section 503.2.7, IECC 2006, as amended by the City of Tucson. |
| 06/09/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 06/09/2009 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 06/09/2009 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 06/09/2009 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | |
| 06/09/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 06/09/2009 | RONALD BROWN | ZONING HC SITE | REVIEW | Approved | |
| 06/09/2009 | RONALD BROWN | ADA | REVIEW | Passed | |
| 06/10/2009 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 06/11/2009 | GERRY KOZIOL | WWM | REVIEW | Passed | |
| 06/11/2009 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |