Permit Number: T09CM01469
Parcel: 13416198B

Address:
7333 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM01469
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/09/2009 STEVE SHIELDS ZONING REVIEW Approved
06/09/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show how the exhaust fan is being connected to the building structure and provide calculations to show that the building structure is not being adversely affected. Reference: Section 302.1, IMC 2006.
2. Resolve the conflict between the note calling for R-6 duct insulation outside and the R-8 insulation called for in detail 101. The minimum insulation for ducts located outside of the building envelope or in a space that freely communicates with the outside is R-8. Reference: Section 503.2.7, IECC 2006, as amended by the City of Tucson.
06/09/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Needs Review
06/09/2009 ROBERT SHERRY WATER REVIEW Approved
06/09/2009 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
06/09/2009 BIANCA RAMIREZ ENGINEERING REVIEW Approved
06/09/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
06/09/2009 RONALD BROWN ZONING HC SITE REVIEW Approved
06/09/2009 RONALD BROWN ADA REVIEW Passed
06/10/2009 MARTIN BROWN FIRE REVIEW Approved
06/11/2009 GERRY KOZIOL WWM REVIEW Passed
06/11/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review