Permit Number: T09CM01381
Parcel: 14117690C

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM01381
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/12/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/12/2009 ERIC NEWCOMB ZONING HC SITE REVIEW Approved
06/12/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
06/12/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Show how the fan coils are being connected to the building structure. The reference drawings indicate that the floor joists are TJI beams; show how the unistrut is to be attached to the TJI. The reference drawings indicate that point loads must be individually verified. Provide calculations to verify that the proposed point load is not adversely affecting the building structure. Reference: Section 302.1, IMC 2006.
06/17/2009 STEVE SHIELDS ZONING REVIEW Approved
07/01/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed IMPACT FEES REQUIRED; SOUTHEAST DISTRICT 2210 SQ FOOT DANCE SCHOOL $14,003.94

Final Status

Task End Date Reviewer's Name Type of Review Description
07/07/2009 DELMA ROBEY OUT TO CUSTOMER Completed