Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T09CM01381
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/12/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
06/12/2009 | ERIC NEWCOMB | ZONING HC SITE | REVIEW | Approved | |
06/12/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
06/12/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Show how the fan coils are being connected to the building structure. The reference drawings indicate that the floor joists are TJI beams; show how the unistrut is to be attached to the TJI. The reference drawings indicate that point loads must be individually verified. Provide calculations to verify that the proposed point load is not adversely affecting the building structure. Reference: Section 302.1, IMC 2006. |
06/17/2009 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
07/01/2009 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Completed | IMPACT FEES REQUIRED; SOUTHEAST DISTRICT 2210 SQ FOOT DANCE SCHOOL $14,003.94 |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
07/07/2009 | DELMA ROBEY | OUT TO CUSTOMER | Completed |