Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T09CM01381
Parcel: 14117690C

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM01381
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/01/2009 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. PROVIDE LATEST APPROVED SITE PLAN.
2. EXISTING STRUCTURAL FRAMING CONFUSING, SOME WALL SECTIONS SHOW TJI'S, SOME SHOW STEEL JOISTS.
3. SHOW NEW WALL BRACING CONNECTION TO STRUCTURE ABOVE, TJI's OR STEEL JOISTS. PROVIDE WEB BRACING FOR TJI'S AS PER MANUFACTURER'S RECCOMMENDATIONS.
06/01/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Show how the temperature of the hot water supply to the public lavatories is controlled. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006.
06/01/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
06/01/2009 RONALD BROWN ZONING HC SITE REVIEW Denied 1. RECEPTION COUNTER NON OMPLIANT WITH 2006 IBC, CHAPTER 11, ICC/ANSI 117.2, SECTION 904.
06/01/2009 PAUL MACHADO ENGINEERING REVIEW Approved
06/01/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Show how the fan coils are being connected to the building structure and provide calculations to show that the building structure is not being adversely affected. Reference: Section 302.1, IMC 2006.
06/01/2009 ROBERT SHERRY WATER REVIEW Approved
06/01/2009 RONALD BROWN ADA REVIEW Passed NOT A COT OWNED/OPERATED PROPERTY
06/02/2009 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: T09CM01381
Building Plan (1st Review)

TRANSMITTAL DATE: June 02, 2009

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Provide a parking calculation for the instructional school based on LUC Section 3.3.4 Motor Vehicle: SA. One (1) space per two hundred (200) sq. ft. GFA or one (1) space per two hundred fifty (250) sq. ft. of office area plus one (1) space per one hundred (100) sq. ft. of classroom area, whichever is greater. This calculation must include all existing tenants.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

C:\planning\grading\t09cm01381.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED:
06/03/2009 MARTIN BROWN FIRE REVIEW Approved
06/11/2009 GERRY KOZIOL WWM REVIEW Approved
06/11/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review