Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T09CM01381
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/01/2009 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. PROVIDE LATEST APPROVED SITE PLAN. 2. EXISTING STRUCTURAL FRAMING CONFUSING, SOME WALL SECTIONS SHOW TJI'S, SOME SHOW STEEL JOISTS. 3. SHOW NEW WALL BRACING CONNECTION TO STRUCTURE ABOVE, TJI's OR STEEL JOISTS. PROVIDE WEB BRACING FOR TJI'S AS PER MANUFACTURER'S RECCOMMENDATIONS. |
06/01/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Show how the temperature of the hot water supply to the public lavatories is controlled. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006. |
06/01/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
06/01/2009 | RONALD BROWN | ZONING HC SITE | REVIEW | Denied | 1. RECEPTION COUNTER NON OMPLIANT WITH 2006 IBC, CHAPTER 11, ICC/ANSI 117.2, SECTION 904. |
06/01/2009 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
06/01/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Show how the fan coils are being connected to the building structure and provide calculations to show that the building structure is not being adversely affected. Reference: Section 302.1, IMC 2006. |
06/01/2009 | ROBERT SHERRY | WATER | REVIEW | Approved | |
06/01/2009 | RONALD BROWN | ADA | REVIEW | Passed | NOT A COT OWNED/OPERATED PROPERTY |
06/02/2009 | STEVE SHIELDS | ZONING | REVIEW | Denied | DSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: T09CM01381 Building Plan (1st Review) TRANSMITTAL DATE: June 02, 2009 1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. Provide a parking calculation for the instructional school based on LUC Section 3.3.4 Motor Vehicle: SA. One (1) space per two hundred (200) sq. ft. GFA or one (1) space per two hundred fifty (250) sq. ft. of office area plus one (1) space per one hundred (100) sq. ft. of classroom area, whichever is greater. This calculation must include all existing tenants. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 C:\planning\grading\t09cm01381.doc RESUBMITTAL OF THE FOLLOWING IS REQUIRED: |
06/03/2009 | MARTIN BROWN | FIRE | REVIEW | Approved | |
06/11/2009 | GERRY KOZIOL | WWM | REVIEW | Approved | |
06/11/2009 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |