Permit Number: T09CM01378
Parcel: 11901076A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM01378
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/02/2009 DAVE MANN FIRE REVIEW Approved
06/04/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SEE PROJECT T09CM01377.
06/05/2009 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/05/2009 ERIC NEWCOMB ZONING HC SITE REVIEW Denied 1. SEE PROJECT T09CM01377.
06/08/2009 GERRY KOZIOL WWM REVIEW Denied future Subway- no wastewater plumbin fixtures in suite- No waster water plumbing fixtures removed per demo drawing
06/15/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide a copy of the approved drawings for the shell package of the building to establish the existing conditions of the tenant space. Reference: Sections 106.1 and 106.3, IBC 2006.
2. Provide energy code compliance calculations (climate zone for Pima County < 4,000 feet). Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope and the mechanical system. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation. Reference: Sections 101.4 and 104.2, International Energy Conservation Code 2006.
3. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Section 503.2, IECC 2006.
4. Provide calculations demonstrating adequate ventilation. Reference: Section 403.1, IMC 2006.
06/22/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Comments with T09CM01377
RTM DSD City of Tucson
6/23/09
06/24/2009 ROBERT SHERRY WATER REVIEW Approved
06/24/2009 RICK MYERS PLUMBING-COMMERCIAL REVIEW Denied 1. Provide material types for all piping. 2. Show how the domestic water is to be sterilized.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/13/2009 GERARDO BONILLA OUT TO CUSTOMER Completed
07/13/2009 SUE REEVES REJECT SHELF Completed