Permit Number: T09CM01377
Parcel: 11901076A

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T09CM01377
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/08/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
09/09/2009 ERIC NEWCOMB ZONING HC REVIEW Approved
09/15/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Comment not resolved; it is the owner's responsibility to maintain the approved drawings. Provide a copy of the approved drawings for the shell package of the building to establish the existing conditions of the tenant space. Reference: Sections 106.1 and 106.3, IBC 2006.
2. Comment not resolved. The information shown on sheet MP-1 indicates that the building does not meet the prescriptive energy code requirements of IECC 2006 due to the SHGC for the windows; the wall are called out as having R-19 insulation but the architectural drawing do not indicate any insulation in the walls; and key note #4 on sheet A2 is ambiguous with regard to the location of the R-30 insulation (see Section 502.2.1, IECC 2006). Provide energy code compliance calculations (climate zone for Pima County < 4,000 feet). Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope and the mechanical system. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation. Reference: Sections 101.4 and 104.2, International Energy Conservation Code 2006.
09/15/2009 DAVE MANN FIRE REVIEW Approved
09/17/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed No new plumbing associated with this activity.
09/18/2009 GERRY KOZIOL WWM REVIEW Denied need wastewater 5th floor credit evaluation for removal of 1 toilet & 1 lav per demo drawings
09/22/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project:3386 S 6th AV T09CM01377
TI

The Electrical Plans have been denied for the following:

1. Last denial dated 6/23/09 item #7 " Provide fault current calculations on let thur to panels" has not been provided. The fault current provided for the SES-1 at Service Section was 27,253 amps sym. The value at the panel determins the AIC the panels are required to be at. Your plan now list the panels at 10,000 amps sym however the calculation at the panels has to be determined.
2. Since last review, the addresses have changed. Now shown on permits are suites 100,110,120. The spaces on plans are 1a,1,2. The panels show A,B.C. Please identify all three the same .All other items ok.
3.This denial includes T09CM011378, and T09Cm01379.


Ray T Majuta
Elect Plan Ck. City of Tucson ,PSDS
9/24/09
Ray.majuta@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
10/27/2009 DELMA ROBEY OUT TO CUSTOMER Completed