Permit Number: T09CM01358
Parcel: 11308011A

Address:
3128 N 1ST AV

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T09CM01358
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/09/2009 DAVE MANN FIRE REVIEW Approved
11/10/2009 GERRY KOZIOL WWM REVIEW Approved
11/10/2009 ROBERT SHERRY WATER REVIEW Denied 1. Provide a vacuum relief for storage-type water heaters located above any fixture outlets. Reference: Section 608.7, UPC 2006.
2. The flow control device for the specified hydromechanical grease interceptor (J. R. Smith #8050) shall be installed in a location that is readily accessible and visible. Reference: Section 1014.2.1, UPC 2006.
3. The discharge of the two 4" roof drains (approximately 150 GPM in a 3" per hour rainstorm) and the overflow drains at the east side of the building with a masonry wall 2'-9" away from the building appears to be contrary to the intent of Section 1803.3, IBC 2006 and Sections 1101.1 and 1101.11.2.2.1, UPC 2006. Show how the storm water is to be directed away from the foundation of the building.
11/13/2009 TERRY STEVENS ZONING REVIEW Denied 11/13/2009

Development Services Department
Zoning Review Section

Terry Stevens
Lead Planner

Comments:

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved site plan. Additional comments may be forthcoming.
11/16/2009 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed Impact Fee's Do Apply; Central District; 4,450 Square Foot Merchantile Building; $20,181.80

Demolition Credits maybe available once demolition permits have been secured.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/19/2009 CPIERCE1 OUT TO CUSTOMER Completed
11/19/2009 SUE REEVES REJECT SHELF Completed