Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T09CM01348
Parcel: 12701005D

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM01348
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/28/2009 MICHAEL ST. PAUL ZONING REVIEW Approved
05/28/2009 JIM MILITELLO MECHANICAL-COMMERCIAL REVIEW Denied 1. Positively pressurized exhaust ducts may not pass through a plenum. Reference: Section 601.4, IMC 2006.
2. Show how the exhaust fan is being connected to the building structure and provide calculations to show that the building structure is not being adversely affected. Reference: Section 302.1, IMC 2006
05/28/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
05/28/2009 JMILITE1 WATER REVIEW Approved
05/28/2009 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
05/28/2009 JMILITE1 WWM REVIEW Passed no new plumbing fixtures.
05/28/2009 JIM MILITELLO PLUMBING-COMMERCIAL REVIEW Passed
05/28/2009 BIANCA RAMIREZ ENGINEERING REVIEW Approved
05/28/2009 DAVE MANN FIRE REVIEW Approved
05/28/2009 RONALD BROWN ZONING HC SITE REVIEW Approved
05/28/2009 RONALD BROWN ADA REVIEW Passed NOT A COT OWNED/OPERATED PROPERTY
06/09/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
06/09/2009 DELMA ROBEY OUT TO CUSTOMER Completed