Permit Number: T09CM01337
Parcel: 99999999A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM01337
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/27/2009 MICHAEL ST. PAUL ZONING REVIEW Approved
05/28/2009 ROBERT SHERRY WATER REVIEW Approved
05/28/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved .
05/28/2009 DAVE MANN FIRE REVIEW Approved
05/28/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved Project: 201 S Williams, T0CM01337
Lobby Revisions

The electrical plans have been denied for the following:

1.Sheet E-100, notes 7,12, and 14 indicate that the contractor to field confirm circuits not overloaded ,will need circuits marked on the plan and show which panels they feed from and the new loads applied to them.
2.Sheet E-200, same as #1.
3. Sheet E-201, same as #2
4. Provide panel schedules and load changes.

Ray T Majuta
Electrical Plans Ex
DSD City of Tucson
520-837-4988
5/28/09
05/28/2009 JIM MILITELLO MECHANICAL-COMMERCIAL REVIEW Approved
06/03/2009 BIANCA RAMIREZ ENGINEERING REVIEW Approved
06/04/2009 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/05/2009 GERRY KOZIOL WWM REVIEW Approved