| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/27/2009 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 05/28/2009 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 05/28/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | . |
| 05/28/2009 | DAVE MANN | FIRE | REVIEW | Approved | |
| 05/28/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | Project: 201 S Williams, T0CM01337 Lobby Revisions The electrical plans have been denied for the following: 1.Sheet E-100, notes 7,12, and 14 indicate that the contractor to field confirm circuits not overloaded ,will need circuits marked on the plan and show which panels they feed from and the new loads applied to them. 2.Sheet E-200, same as #1. 3. Sheet E-201, same as #2 4. Provide panel schedules and load changes. Ray T Majuta Electrical Plans Ex DSD City of Tucson 520-837-4988 5/28/09 |
| 05/28/2009 | JIM MILITELLO | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 06/03/2009 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | |
| 06/04/2009 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 06/05/2009 | GERRY KOZIOL | WWM | REVIEW | Approved |