Permit Number: T09CM01334
Parcel: 10705126B

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T09CM01334
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/21/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
12/21/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Tucson Water limits the demand on a 2" meter to 80 GPM. Contact Fred Coy of Tucson Water (837-2220) for approval to use a 2" meter for a demand of 96 GPM.
2. Provide pressure-absorbing devices for the water connections to the clothes washer. Reference: Section 609.10, UPC 2006.
3. Clarify the locations for applying riser diagram F/P-3 versus riser diagrams E/P-3 and E/P-4. Reference: Section 103.2.3, UPC 2006.
12/28/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied See comments for T09CM01333.
RTM<Elect Pln CK,12/29/09

Final Status

Task End Date Reviewer's Name Type of Review Description
01/06/2010 SUE REEVES OUT TO CUSTOMER Completed
01/06/2010 SUE REEVES REJECT SHELF Completed