Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T09CM01333
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/18/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 12/18/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Tucson Water limits the demand on a 2" meter to 80 GPM. Contact Fred Coy of Tucson Water (837-2220) for approval to use a 2" meter for a demand of 82 GPM. 2. Provide pressure-absorbing devices for the water connections to the clothes washer. Reference: Section 609.10, UPC 2006. |
| 12/28/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project: 801 W Miracle Mile Apartment Remodel T09CM01333 The electrical plans have been denied for the following: 1. In review of the previous load calculations for individual panels, same appliance loads are different than these submitted. The DW<DISP<WH<INDOOR UNIT<OUTDOOR UNIT loads have gone down on this calculation.Since a washer and dryer are being added,the total load decreases.Explain the reason for decrease. 2. Note on plan how many A units are having washer and dryer's added on Building #9, also on Building #10. 3. Provide a cut sheet on stackable dryer/washer showing one circuit (30a/2pole) sufficient for both. Ray T Majuta PDSD, City of Tucson Elect Pln Ck 12/29/09 Ray.Majuta@tucsonaz.gov |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/06/2010 | SUE REEVES | OUT TO CUSTOMER | Completed |
| 01/06/2010 | SUE REEVES | REJECT SHELF | Completed |