Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T09CM01328
Parcel: 126130170

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM01328
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/27/2009 TERRY STEVENS ZONING REVIEW Approved
05/27/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
05/27/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
05/27/2009 ROBERT SHERRY WATER REVIEW Approved
05/27/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/27/2009 RSHERRY1 WWM REVIEW Passed No new plumbing fixtures.
05/27/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
05/27/2009 PAUL MACHADO ENGINEERING REVIEW Approved
05/27/2009 DAVE MANN FIRE REVIEW Approved
05/27/2009 ERIC NEWCOMB ZONING HC SITE REVIEW Approved
05/27/2009 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/27/2009 ERIC NEWCOMB ADA REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
05/27/2009 DELMA ROBEY OUT TO CUSTOMER Completed