Permit Number: T09CM01281
Parcel: 12109006A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T09CM01281
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/11/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Comment not resolved; detail 105/M-3 references the "structural drawings" for information on how to connect the hoods to the building structure but no structural drawings cover the issue and the drawings have been unchanged since 3/27/09. Show how the hoods are being connected to the building structure (e.g. the wood I-beams). Reference: Section 302.1, IMC 2006.
Note: resolution of this issue may be done over-the-counter.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/19/2010 DELMA ROBEY OUT TO CUSTOMER Completed
01/19/2010 SUE REEVES REJECT SHELF Completed