| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/11/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Comment not resolved; detail 105/M-3 references the "structural drawings" for information on how to connect the hoods to the building structure but no structural drawings cover the issue and the drawings have been unchanged since 3/27/09. Show how the hoods are being connected to the building structure (e.g. the wood I-beams). Reference: Section 302.1, IMC 2006. Note: resolution of this issue may be done over-the-counter. |