Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T09CM01281
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/08/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 01/08/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 01/08/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Comment not resolved; detail 105/M-3 references the "structural drawings" for information on how to connect the hoods to the building structure but no structural drawings cover the issue and the drawings have been unchanged since 3/27/09. Show how the hoods are being connected to the building structure. Reference: Section 302.1, IMC 2006. 2. TUSD is required to comply with the Arizona State Fire Code which also requires a Type I hood. The installation of a Type I hood shall be per the current mechanical code. The kitchen equipment list (A-4) shows a 2-burner range, a convection oven, and a combi-oven under hood H-1. Hood H-1 must be a Type I hood. Reference: Section 507.2, IMC 2006. 3. TUSD is required to comply with the Arizona State Fire Code which also requires a Type I hood. The installation of a Type I hood shall be per the current mechanical code. Verify that the walls adjacent to hood H-1 comply with the requirements of Section 507.9, IMC 2006. |
| 12/23/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 12/23/2009 | ERIC NEWCOMB | ZONING HC | REVIEW | Approved |