Permit Number: T09CM01281
Parcel: 12109006A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T09CM01281
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/08/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
01/08/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
01/08/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Comment not resolved; detail 105/M-3 references the "structural drawings" for information
on how to connect the hoods to the building structure but no structural drawings cover
the issue and the drawings have been unchanged since 3/27/09. Show how the hoods are
being connected to the building structure. Reference: Section 302.1, IMC 2006.
2. TUSD is required to comply with the Arizona State Fire Code which also requires
a Type I hood. The installation of a Type I hood shall be per the current mechanical
code. The kitchen equipment list (A-4) shows a 2-burner range, a convection oven,
and a combi-oven under hood H-1. Hood H-1 must be a Type I hood. Reference: Section
507.2, IMC 2006.
3. TUSD is required to comply with the Arizona State Fire Code which also requires
a Type I hood. The installation of a Type I hood shall be per the current mechanical
code. Verify that the walls adjacent to hood H-1 comply with the requirements of Section
507.9, IMC 2006.
12/23/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
12/23/2009 ERIC NEWCOMB ZONING HC REVIEW Approved