Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T09CM01281
Parcel: 12109006A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM01281
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/27/2009 RONALD BROWN ADA REVIEW Passed NOT A COT OWNED/OPERATED PROPERTY
05/27/2009 DAVE MANN FIRE REVIEW Denied Sheets E-4, E-8
The Automatic fire detectors shall be smoke detector unless prohibited by ambient conditions. IFC 907.2.
05/27/2009 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/29/2009 GERRY KOZIOL WWM REVIEW Approved
06/02/2009 RONALD BROWN ZONING HC SITE REVIEW Denied REFERENCE BUILDING COMMENTS
06/03/2009 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 3 JUNE 2009
T09CM01241/FT. LOWELL ELEMENTARY SCHOOL
REVIEWED BY RON BROWN

BUILDING AND ACCESSIBLE REVIEW
2006 IBC/ICC/ANSI 117.1

DENIED: SEE COMMENTS BELOW

I. GENERAL:
A. Provide new construction structural calculations and include load calculations for new roof top mounted HVAC equipment.
B. Provide the most recently approved Site Plan.
C. Provide a Site Plan showing all the new additions and outside changes for accessibility entrances.
1. Provide up dated parking changes as required.
2. Provide up dated occupancy load calculations.
3. Provide up dated toilet fixture count.
4. Provide completed Special Inspection forms for approval.
II. SHEET S1.2:
A. Provide a letter to the building official, Mr. Ernie Duarte outlining all deferred Submittals.
III. SHEET D-2:
A. Correct note shown several places on the Demolition Elevations, "New construction to demolish".
IV. SHEET A-1:
A. Is Room 112 really an "OFFICE"? Maybe it should read "VESTIBULE".
B. Add reference mark "14/A15" for large scale toilet area plan.
C. Where is the mop sink?
D. Where are the EWCs?
E. Add elevation references 4/A14 and 5/A15 to the new Reception counter.
V. SHEET A-2:
A. NEW PARTIAL KITCHEN PLAN:
1. Provide a stainless steel finish on the wall behind the exhaust hood.
2. The newly constructed Toilet Room 205 must be accessible as per 2006 IBC, Section 3409.6.
3. At Detail 2/A-2, the landing and concrete slopes at the rear kitchen door must be accessible. The slopes may be no more than 5%. If slopes are more than 5% then a ramp must be provided complying with ICC/ANSI 117.7, Section 405. Provide all handrails and 5'x5' clear space landings as per section 405.7 and 405.8.
VI. SHEET A-3:
A. At notes number 13 and 49, change A-13 to A-14
B. At both notes number 15, add a stainless steel finish.
VII. SHEET A-8:
A. Section DD: Redraw roof drain to show draining into roof drain down spout separate from the scupper down spout.
VIII. SHEET A-15:
A. Provide Detail Title number 14 for the toilet floor plan.
B. Provide Detail Title number 15 for the Toilet Accessory Mounting Heights.
C. At Detail 14/A-15:
1. Toilet 108 is not accessible compliant to ICC/ANSI 117.1, Section 604.3, lav encroachment on toilet clear space.
2. Where are the EWC's.
3. Provide the critical clearance dimensions for all toilet rooms.
D. At Detail 15/A-15:
1. Most all dimensions for the accessories around the toilet are incorrect. Revise all dimensions to ICC/ANSI 117.1 standards as depicted by Section 604.
2. Most all dimensions for the accessories around the lav are incorrect. Revise all dimensions to ICC/ANSI 117.1 standards as depicted by Section 606
IX. SHEET A-16:
A. At the Door Schedule:
1. Insure that all exit doors have panic bars as required by 2006 IBC, Section 1008.1.9
2. Provide the vertical dimensions from finished floor to header for Door "E" on door "E" elevation.

END OF REVIEW
06/05/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: 5151 E Pima ST
T09CM01281
Elem School Kitchen Remodel

Electrical Plans have been denied for the following:

1. Sheet E-5 states on key note # 2, refer to mech drawings for inter-connections with AC and control of exhaust fan. Not enough information is given to review how inter -connect is to be made. Provide a diagram showing how inter-lock is to be made,show where control panel will be located, and how other items to be connected. What circuit will the control panel be fed from ? Will there be a shunt trip breaker involved ? Hood installer may provide what type of equipment is to be used.


Ray T Majuta
City of Tucson DSD
Elect Plan CK
6/07/09
520-837-4988
06/18/2009 ROBERT SHERRY WATER REVIEW Approved
06/18/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show how the hoods are being connected to the building structure. Reference: Section 302.1, IMC 2006.
2. Show the size, routing, and termination of the condensate drain for AC-1. Reference: Section 307.2, IMC 2006 and Section 814.0, UPC 2006.
3. Provide calculations to show that the common ventilation system for the areas served by AC-1 is sized in accordance with Section 403.3.2, IMC 2006.
4. Provide energy code compliance calculations for the building additions. Reference: Section 101.4, International Energy Conservation Code 2006.
5. Insulation installed on a suspended ceiling with removable tiles cannot be counted as part of the roof insulation. Reference: Section 502.2.1, IECC 2006.
06/22/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide updated water calculations or a copy of the calculations that were used for the shell building. Reference: Sections 103.2.3 and 610.1, UPC 2006.
2. Clarify the design for the roof drainage for the new kitchen roof. Detail 1/A-8 shows an un-sized roof drain (primary drain) along with a scupper (secondary drain) but the roof plan on sheet A-10 does not show any roof drains. Reference: Sections 103.2.3 and 1101.11, UPC 2006.
3. The minimum opening width for a scupper is 6.25", based on a 2" roof drain requirement. Reference: Section 1101.11.2.1, UPC 2006.
4. Detail 1/A-8 indicates a "metl (sic) bug screen" enclosing the entry to the scupper. Show that the open area of the screen is at least 1.5 times greater than the minimum area of the scupper (4" x 6.25"). Reference: Sections 1101.11.2.1 and 1105.2, UPC 2006.
5. Show how the termination of the secondary (overflow) rainwater leader is clearly observable by the building occupants or maintenance personnel. Reference: Section 1101.11.2.2.1, UPC 2006.
6. Provide the rim elevation of the next upstream sanitary manhole (FFE = 2484.86'). Determine the need for a backwater valve per Section 710.1, UPC 2006, as amended by the City of Tucson.
7. Clarify the nature of the flow control device for the proposed hydromechanical grease interceptor (i.e. is it integral to the interceptor or is it external; detail 214/P2.3 indicates a grease interceptor with an external flow control device). One flow control device shall be provided for each fixture connected to the grease interceptor and each external flow control device shall be readily accessible and visible. Reference: Sections 103.2.3 and 1014.2.1, UPC 2006.
8. Clarify the reason for locating a floor drain (P5) on the exterior of the building and show how rainwater will be kept out of the grease waste system. Reference: Section 306.2, UPC 2006.
9. Coordinate the number of water heaters (WH-1) to be used for the kitchen; the Architectural and mechanical backgrounds show two units. Reference: Section 103.2.3, UPC 2006.
10. Provide combustion air openings for water heater WH-1. Reference: Section 507, UPC 2006.
11. Provide a design for the flue for WH-1 and show that the termination of the flue complies with the requirements of Section 510.6.2, UPC 2006. Reference: Section 103.2.3, UPC 2006.
12. Show the size of the T&P relief piping from WH-1. Reference: Section 608.5, UPC 2006.
13. Show the size, route and termination of T&P relief piping from WH-2. Reference: Section 608.5, UPC 2006.
14. Clarify why detail 213 calls for the drain of the booster heater to be routed to the floor drain, P-5. Reference: Section 103.2.3, UPC 2006.
15. Provide a floor drain in the scullery area of the kitchen. Reference: Sections 411.2.2 and 704.3, UPC 2006.
16. Provide pressure-absorbing devices for the water connections to appliances equipped with quick-acting or solenoid valves (e.g. the dishwasher and the spray rinse). Reference: Section 609.10, UPC 2006.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/05/2009 CINDY AGUILAR OUT TO CUSTOMER Completed
08/05/2009 SUE REEVES REJECT SHELF Completed