Permit Review Detail
Review Status: Completed
Review Details: POST 3RD PARTY REVIEW
Permit Number - T09CM01279
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/07/2009 | DAVE MANN | FIRE | REVIEW | Approved | |
10/08/2009 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
10/08/2009 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
10/09/2009 | ROBERT SHERRY | WATER | REVIEW | Denied | 1. Revise the size of the scuppers to comply with the requirements of Section 1101.11.2.1, UPC 2006. 2. Show the total area drained by each scupper and by each roof drain/overflow drain to verify the indicated size selected for each device.. 3. Revise the overflow drains to include a strainer. Reference: Section 1105.2, UPC 2006. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
10/21/2009 | SUE REEVES | OUT TO CUSTOMER | Completed |