Permit Number: T09CM01279
Parcel: 11301146Z

Address:
1763 E PRINCE RD

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T09CM01279
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/07/2009 DAVE MANN FIRE REVIEW Approved
10/08/2009 STEVE SHIELDS ZONING REVIEW Approved
10/08/2009 LOREN MAKUS ENGINEERING REVIEW Approved
10/09/2009 ROBERT SHERRY WATER REVIEW Denied 1. Revise the size of the scuppers to comply with the requirements of Section 1101.11.2.1, UPC 2006.
2. Show the total area drained by each scupper and by each roof drain/overflow drain to verify the indicated size selected for each device..
3. Revise the overflow drains to include a strainer. Reference: Section 1105.2, UPC 2006.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/21/2009 SUE REEVES OUT TO CUSTOMER Completed