Permit Number: T09CM01269
Parcel: 107031840

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM01269
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/19/2009 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
05/19/2009 DAVE MANN FIRE REVIEW Approved
05/19/2009 RONALD BROWN ZONING HC SITE REVIEW Approved
05/20/2009 GERRY KOZIOL WWM REVIEW Approved
05/20/2009 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/02/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
06/04/2009 ROBERT SHERRY WATER REVIEW Approved
06/04/2009 RICK MYERS PLUMBING-COMMERCIAL REVIEW Denied 1. Provide "Petition Of Appeal" for the use of the International Plumbing Code. 2. Per sheet P-3.0 detail 4, show approved location of T & P relief drain termination. 3. Per sheet P-3.0 detail one, waste and vent isometric diagram, only 20 DFUs allowed on a 2" vent. Reference table 916.1 2006 IPC. 4. Include in the Plumbing General Notes the method of sterilization to be used in the domestic water system. Reference 610 2006 IPC.
06/04/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show the location of the unit heater vents on the 2nd floor plan. Confirm that the location of the vent conforms to the separation from the intake openings of the evaporative coolers as required in Section 401.4.1, IMC 2006.
2. Show how the unit heaters are being connected to the building structure and provide calculations to show that the building structure is not being adversely affected. Reference: Section 302.1, IMC 2006.
06/10/2009 MICHAEL ST. PAUL ZONING REVIEW Approved