Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T09CM01269
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/19/2009 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 05/19/2009 | DAVE MANN | FIRE | REVIEW | Approved | |
| 05/19/2009 | RONALD BROWN | ZONING HC SITE | REVIEW | Approved | |
| 05/20/2009 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 05/20/2009 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 06/02/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 06/04/2009 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 06/04/2009 | RICK MYERS | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide "Petition Of Appeal" for the use of the International Plumbing Code. 2. Per sheet P-3.0 detail 4, show approved location of T & P relief drain termination. 3. Per sheet P-3.0 detail one, waste and vent isometric diagram, only 20 DFUs allowed on a 2" vent. Reference table 916.1 2006 IPC. 4. Include in the Plumbing General Notes the method of sterilization to be used in the domestic water system. Reference 610 2006 IPC. |
| 06/04/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show the location of the unit heater vents on the 2nd floor plan. Confirm that the location of the vent conforms to the separation from the intake openings of the evaporative coolers as required in Section 401.4.1, IMC 2006. 2. Show how the unit heaters are being connected to the building structure and provide calculations to show that the building structure is not being adversely affected. Reference: Section 302.1, IMC 2006. |
| 06/10/2009 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved |