Permit Number: T09CM01258
Parcel: 117141070

Address:
58 W CUSHING ST

Review Status: Completed

Review Details: RESUBMITTAL - SITE ALL

Permit Number - T09CM01258
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/31/2009 STEVE SHIELDS ZONING REVIEW Approved
08/05/2009 RONALD BROWN ZONING HC SITE REVIEW Approved
08/11/2009 JASON GREEN ENGINEERING REVIEW Approved DATE: August 11, 2009
SUBJECT: 58 W Cushing St Site Plan- 2nd Engineering Review
TO: Marvin Shaver
LOCATION: T14S R13E Sec13 Ward 6
REVIEWERS: Jason Green, CFM
ACTIVITY: T09CM01258 (Site/Building Plan)

SUMMARY: Engineering Division of Development Services Department has received and reviewed the site plan (T09CM01258) and building plan (T09CM01258) applications for the above referenced property. Engineering Division recommends approval of the plan sets at this time.

SITE PLAN COMMENTS:

1) Complied.

2) Complied.

3) Complied.

4) Complied.

5) Complied.

6) Complied.

7) Complied.

BUILDING PLAN COMMENTS:

8) Complied.

9) Complied.

GENERAL COMMENTS:

For questions, or to schedule an appointment, I can be reached at 837-4929.


Jason Green, CFM
Senior Engineer Associate
Engineering Division
COT Development Services
08/17/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not resolved Revise the site drawing to show the location and size of both the water meter and the reduced pressure backflow preventer assembly. Reference: Section 103.2.3, UPC 2006.
2. Comment not addressed. Where the finish floor elevation is less than 12 inches above the elevation of the next upstream manhole in the public sewer or private sewer collection system, a backwater valve shall be installed in the building drain or branch of the building drain serving that floor. Floors discharging from above that reference point shall not discharge through the backwater valve. Reference: Section 710.1, UPC 2006, as amended by the City of Tucson.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/18/2009 THAUSER1 OUT TO CUSTOMER Completed
08/18/2009 SUE REEVES REJECT SHELF Completed