Permit Number: T09CM01258
Parcel: 117141070

Address:
58 W CUSHING ST

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T09CM01258
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/30/2009 RONALD BROWN ADA REVIEW Passed Not a COT owned/operated property
07/31/2009 STEVE SHIELDS ZONING REVIEW Approved
08/04/2009 RONALD BROWN ZONING HC SITE REVIEW Approved
08/04/2009 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Section 5/A2.0 needs to be coordinated with modified roof design of detail numbers 1/A2.0, 2/A1.0 and 2/A3.0.
2. Please provide a detail at the joist bearing seat above the new 3' wide exterior door.
3. Please correct Roof Plan Detail 3/A2.0 to have two scuppers on the East side as per Elevation 1/A2.0 and existing roof drainage calculations.

END OF REVIEW
08/11/2009 JASON GREEN ENGINEERING REVIEW Approved DATE: August 11, 2009
SUBJECT: 58 W Cushing St Site Plan- 2nd Engineering Review
TO: Marvin Shaver
LOCATION: T14S R13E Sec13 Ward 6
REVIEWERS: Jason Green, CFM
ACTIVITY: T09CM01258 (Site/Building Plan)

SUMMARY: Engineering Division of Development Services Department has received and reviewed the site plan (T09CM01258) and building plan (T09CM01258) applications for the above referenced property. Engineering Division recommends approval of the plan sets at this time.

SITE PLAN COMMENTS:

1) Complied.

2) Complied.

3) Complied.

4) Complied.

5) Complied.

6) Complied.

7) Complied.

BUILDING PLAN COMMENTS:

8) Complied.

9) Complied.

GENERAL COMMENTS:

For questions, or to schedule an appointment, I can be reached at 837-4929.


Jason Green, CFM
Senior Engineer Associate
Engineering Division
COT Development Services
08/17/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The overflow scuppers shown on the plans appear to be the same height above the roof. Per Section 1101.11.2.2, UPC 2006, the secondary drain shall be a minimum of 2" above the low point of the roof.
08/17/2009 ROBERT SHERRY WATER REVIEW Approved
08/17/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied The condensate will be produced at the indoor coil, not at the condensing unit. Show the actual routing of the condensate drain. Reference: Section 307.2, IMC 2006 and Section 814.0, UPC 2006.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/18/2009 THAUSER1 OUT TO CUSTOMER Completed
08/18/2009 SUE REEVES REJECT SHELF Completed