Permit Number: T09CM01258
Parcel: 117141070

Address:
58 W CUSHING ST

Review Status: Completed

Review Details: SITE

Permit Number - T09CM01258
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/17/2009 RBROWN1 ADA REVIEW Passed NOT A COT OWNED/OPERATED PROPERTY
06/17/2009 RONALD BROWN ZONING HC SITE REVIEW Denied 1. RELOCATING THE ACCESSIBLE PARKING TO THE WEST SIDE OF THE PARKING LOT AND PROVIDING AN ACCESSIBLE AISLE ADJACENT TO THE NEW ADDITION WITH DIRECT ACCESS FROM THE AISLE TO THE NEW ENTRANCE PORCH IS A MUCH BETTER SOLUTION THAN HAVING THE ACCESSIBLE PARKING ON THE EAST SIDE WITH A HAZARDOUS PAAL CROSSING TO ACCESS THE REAR ENTRY WAY. THE SUGGESTED CHANGE WILL STILL PROVUIDE 12 PARKING SPACES. IF ZONING ACCEPTS THE GENERAL NON COMPLIANT PAAL WIDTH OF LESS THAN 24', THEN THE ACCESS CORNER FROM THE PATIO TO THE EDGE OF THE EAST SIDE PARKING COULD BE WIDEN BY ROUNDING OFF THE 90 DEGREE CORNER OF THE BRICK PATIO MAKING THE VEHICLE WIDTH DIMENSION SOMEWHERE AROUND 18' TO 19', MORE THAN THE SIDE ACCESS DRIVE WIDTH AT THE EXISTING BUILDING. SEE SUGGESTED SKETCH PROVIDED ON SITE PLAN.
2. A MINIMUM OF 54" WIDE CLEARANCE IS REQUIRED FOR THE ACCESS TO THE REAR DOOR BETWEEN THE WALL AND THE COLUMN IF DOOR HAS A CLOSER, REFERENCE SECTION 404.2.3.1 (F).
06/19/2009 MARTIN BROWN FIRE REVIEW Approved
06/22/2009 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Cushing Street Family Practice - Expansion
T09CM01258
Site Plan (1st Review)

TRANSMITTAL DATE: June 22, 2009

COMMENTS: Please resubmit revised drawings and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. This site plan was reviewed for compliance with the City of Tucson Development Standards (D.S.) and Land Use Code (LUC). Per D.S. 2-02.2.2.B for full code compliance for the area of expansion only.

2. D.S. 2-02.2.1.A.5 Provide the lot bearings on the site plan.

3. D.S. 2-02.2.1.A.8 The proposed handicapped parking location presents a safety hazard. Zoning recommends that the parking be revised as shown on the red lines provided by the accessible reviewer.

4. D.S. 2-02.2.1.A.8 Provide wheel stops per D.S. 3-05.2.3.C.2 and D.S. 3-05.0 Figure 5 for all parking spaces to protect the existing fence.

5. D.S. 2-02.2.1.A.10 Show the existing sight visibility triangles (SVTs) on the plan.

6. D.S. 2-02.2.1.A.11 Provide a parking area access lane dimension from the southeast corner of the existing pavers to the northern most parking space located along the east property line.

7. D.S. 2-02.2.1.A.31 Provide the "Subject to LUC Section 3.5.4.8.B" adjacent to the use.

8. Depending on how the above comments are addressed addition comments may be forth coming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956.

C:\planning\site\t09cm01258

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents.
06/24/2009 JASON GREEN ENGINEERING REVIEW Denied DATE: June 24, 2009
SUBJECT: 58 W Cushing St Site Plan- Engineering Review
TO: Marvin Shaver
LOCATION: T14S R13E Sec13 Ward 6
REVIEWERS: Jason Green, CFM
ACTIVITY: T09CM01258 (Site/Building Plan)

SUMMARY: Engineering Division of Development Services Department has received and reviewed the site plan (T09CM01258) and building plan (T09CM01258) applications for the above referenced property. Engineering Division does not recommend approval of the plan sets at this time. The following items need to be addressed:

SITE PLAN COMMENTS:

1) DS Sec.2-02.2.1.A.5: Revise the site plan to label the bearings for the dimensions provided for the property boundaries.

2) DS Sec.2-02.2.1.A.8: Revise the site plan to provide for the required wheel stops to prevent vehicles from encroaching into the existing fence surrounding the property. If the parking spaces are proposed at 18-feet then wheel stops will be required to allow for the required 2.5 foot overhang at these areas.

3) DS Sec.2-02.2.1.A.10: Revise the site plan to label and dimension the sight visibility triangles for the intersection of the PAAL access and Cushing Street. Provide the dimension for the near side of the triangle per DS Sec.3-01.5.3.

4) DS Sec.2-02.2.1.A.12: Refer to comments from Ron Brown, RA Structural Plans Examiner for all onsite handicap and ADA requirements that apply to this project.

5) DS Sec.2-02.2.1.A.19: Revise the site plan to label Cushing Street as "MS&R Route and Public Street."

6) DS Sec.2-02.2.1.A.19: Revise the site plan to label the shown right-of-way as "Existing/Future."

7) Be advised that further comments may be forth coming on resubmittal of the site plan.

BUILDING PLAN COMMENTS:

8) Engineering could not verify that the building plan was in compliance with a stamped approved site plan (T09CM01258). Please submit two copies of the stamped approved site plan with the next building plan submittal.

9) Engineering will re-review the building plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming.

GENERAL COMMENTS:

Please provide a revised site plan that addresses the comments provided above. Include a comprehensive response letter addressing in detail responses to all of the above comments. Enclose "redlines" with the resubmittal package.

Further comments may be generated upon resubmittal of the site plan review.

For questions, or to schedule an appointment, I can be reached at 837-4929.



Jason Green, CFM
Senior Engineer Associate
Engineering Division
COT Development Services
07/02/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the site drawing to show the location and size of both the water meter and the reduced pressure backflow preventer assembly. Reference: Section 103.2.3, UPC 2006.
2. Where the finish floor elevation is less than 12 inches above the elevation of the next upstream manhole in the public sewer or private sewer collection system, a backwater valve shall be installed in the building drain or branch of the building drain serving that floor. Floors discharging from above that reference point shall not discharge through the backwater valve. Reference: Section 710.1, UPC 2006, as amended by the City of Tucson.
07/07/2009 PETER MCLAUGHLIN LANDSCAPE REVIEW Approved
07/07/2009 PETER MCLAUGHLIN NPPO REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
07/14/2009 CINDY AGUILAR OUT TO CUSTOMER Completed
07/14/2009 SUE REEVES REJECT SHELF Completed