Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T09CM01258
Parcel: 117141070

Address:
58 W CUSHING ST

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM01258
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/17/2009 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Door to office non-accessible as to ICC/ANSI 117.2 Section 404.2.2
2. Exterior 3' wide exit door needs 1'-0" inside strike jamb clearance as per ICC/ANSI/117.1, Section 404.2.3.1.
3. Provide structural calculations for foundations, roof framing and all roff mounted HVAC units.
4. Provide Roof mounted HVAC unit mounting and connection details.

END OF REVIEW
06/17/2009 RONALD BROWN ZONING HC SITE REVIEW Denied REFERENCE BUILDING COMMENTS
06/17/2009 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed Impact Fee's Do Apply; Central District; 225 Square Foot Addition; $1,207.63
06/19/2009 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Cushing Street Family Practice - Expansion
T09CM01258
Building Plan (1st Review)

TRANSMITTAL DATE: June 22, 2009

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved site plan.. Please submit two copies of the approved and stamped site plan with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

C:\planning\grading\t09cm01258.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED:
06/19/2009 MARTIN BROWN FIRE REVIEW Approved
06/24/2009 JASON GREEN ENGINEERING REVIEW Denied DATE: June 24, 2009
SUBJECT: 58 W Cushing St Site Plan- Engineering Review
TO: Marvin Shaver
LOCATION: T14S R13E Sec13 Ward 6
REVIEWERS: Jason Green, CFM
ACTIVITY: T09CM01258 (Site/Building Plan)

SUMMARY: Engineering Division of Development Services Department has received and reviewed the site plan (T09CM01258) and building plan (T09CM01258) applications for the above referenced property. Engineering Division does not recommend approval of the plan sets at this time. The following items need to be addressed:

SITE PLAN COMMENTS:

1) DS Sec.2-02.2.1.A.5: Revise the site plan to label the bearings for the dimensions provided for the property boundaries.

2) DS Sec.2-02.2.1.A.8: Revise the site plan to provide for the required wheel stops to prevent vehicles from encroaching into the existing fence surrounding the property. If the parking spaces are proposed at 18-feet then wheel stops will be required to allow for the required 2.5 foot overhang at these areas.

3) DS Sec.2-02.2.1.A.10: Revise the site plan to label and dimension the sight visibility triangles for the intersection of the PAAL access and Cushing Street. Provide the dimension for the near side of the triangle per DS Sec.3-01.5.3.

4) DS Sec.2-02.2.1.A.12: Refer to comments from Ron Brown, RA Structural Plans Examiner for all onsite handicap and ADA requirements that apply to this project.

5) DS Sec.2-02.2.1.A.19: Revise the site plan to label Cushing Street as "MS&R Route and Public Street."

6) DS Sec.2-02.2.1.A.19: Revise the site plan to label the shown right-of-way as "Existing/Future."

7) Be advised that further comments may be forth coming on resubmittal of the site plan.

BUILDING PLAN COMMENTS:

8) Engineering could not verify that the building plan was in compliance with a stamped approved site plan (T09CM01258). Please submit two copies of the stamped approved site plan with the next building plan submittal.

9) Engineering will re-review the building plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming.

GENERAL COMMENTS:

Please provide a revised site plan that addresses the comments provided above. Include a comprehensive response letter addressing in detail responses to all of the above comments. Enclose "redlines" with the resubmittal package.

Further comments may be generated upon resubmittal of the site plan review.

For questions, or to schedule an appointment, I can be reached at 837-4929.



Jason Green, CFM
Senior Engineer Associate
Engineering Division
COT Development Services
06/29/2009 GERRY KOZIOL WWM REVIEW Passed
07/02/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide energy code compliance calculations. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation. Reference: Sections 101.4 and 104.2, International Energy Conservation Code 2006.
2. Show the size, routing, and termination of the condensate drains. Reference: Section 307.2, IMC 2006 and Section 814.0, UPC 2006.
07/06/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The applicable code for all commercial plumbing projects is the 2006 Uniform Plumbing Code with Local Amendments.
2. Provide overflow protection for the existing roof in which a new 12"x4" scupper is being installed. Reference: Section 1101.11, UPC 2006.
3. Provide hydraulic calculations to show that the proposed 4" diameter scuppers provide the capacity equivalent to the code-required minimum 6.25"x 4" scuppers. Reference: Sections 1101.11 and 1106.0, UPC 2006.
4. Provide overflow protection for the new roof. Reference: Section 1101.11, UPC 2006.
07/06/2009 ROBERT SHERRY WATER REVIEW Denied Reduced pressure backflow prevention assemblies are required at the water meter for multi-use commercial buildings. Reference: COT Ordinance 9976, http://www.tucsonaz.gov/water/docs/backflow-ord.pdf.
07/13/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/14/2009 CINDY AGUILAR OUT TO CUSTOMER Completed
07/14/2009 SUE REEVES REJECT SHELF Completed