Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T09CM01258
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/17/2009 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Door to office non-accessible as to ICC/ANSI 117.2 Section 404.2.2 2. Exterior 3' wide exit door needs 1'-0" inside strike jamb clearance as per ICC/ANSI/117.1, Section 404.2.3.1. 3. Provide structural calculations for foundations, roof framing and all roff mounted HVAC units. 4. Provide Roof mounted HVAC unit mounting and connection details. END OF REVIEW |
06/17/2009 | RONALD BROWN | ZONING HC SITE | REVIEW | Denied | REFERENCE BUILDING COMMENTS |
06/17/2009 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Completed | Impact Fee's Do Apply; Central District; 225 Square Foot Addition; $1,207.63 |
06/19/2009 | STEVE SHIELDS | ZONING | REVIEW | Denied | DSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: Cushing Street Family Practice - Expansion T09CM01258 Building Plan (1st Review) TRANSMITTAL DATE: June 22, 2009 1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. Zoning could not verify that the building plan was in compliance with the approved site plan.. Please submit two copies of the approved and stamped site plan with the next building plan submittal. 3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 C:\planning\grading\t09cm01258.doc RESUBMITTAL OF THE FOLLOWING IS REQUIRED: |
06/19/2009 | MARTIN BROWN | FIRE | REVIEW | Approved | |
06/24/2009 | JASON GREEN | ENGINEERING | REVIEW | Denied | DATE: June 24, 2009 SUBJECT: 58 W Cushing St Site Plan- Engineering Review TO: Marvin Shaver LOCATION: T14S R13E Sec13 Ward 6 REVIEWERS: Jason Green, CFM ACTIVITY: T09CM01258 (Site/Building Plan) SUMMARY: Engineering Division of Development Services Department has received and reviewed the site plan (T09CM01258) and building plan (T09CM01258) applications for the above referenced property. Engineering Division does not recommend approval of the plan sets at this time. The following items need to be addressed: SITE PLAN COMMENTS: 1) DS Sec.2-02.2.1.A.5: Revise the site plan to label the bearings for the dimensions provided for the property boundaries. 2) DS Sec.2-02.2.1.A.8: Revise the site plan to provide for the required wheel stops to prevent vehicles from encroaching into the existing fence surrounding the property. If the parking spaces are proposed at 18-feet then wheel stops will be required to allow for the required 2.5 foot overhang at these areas. 3) DS Sec.2-02.2.1.A.10: Revise the site plan to label and dimension the sight visibility triangles for the intersection of the PAAL access and Cushing Street. Provide the dimension for the near side of the triangle per DS Sec.3-01.5.3. 4) DS Sec.2-02.2.1.A.12: Refer to comments from Ron Brown, RA Structural Plans Examiner for all onsite handicap and ADA requirements that apply to this project. 5) DS Sec.2-02.2.1.A.19: Revise the site plan to label Cushing Street as "MS&R Route and Public Street." 6) DS Sec.2-02.2.1.A.19: Revise the site plan to label the shown right-of-way as "Existing/Future." 7) Be advised that further comments may be forth coming on resubmittal of the site plan. BUILDING PLAN COMMENTS: 8) Engineering could not verify that the building plan was in compliance with a stamped approved site plan (T09CM01258). Please submit two copies of the stamped approved site plan with the next building plan submittal. 9) Engineering will re-review the building plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming. GENERAL COMMENTS: Please provide a revised site plan that addresses the comments provided above. Include a comprehensive response letter addressing in detail responses to all of the above comments. Enclose "redlines" with the resubmittal package. Further comments may be generated upon resubmittal of the site plan review. For questions, or to schedule an appointment, I can be reached at 837-4929. Jason Green, CFM Senior Engineer Associate Engineering Division COT Development Services |
06/29/2009 | GERRY KOZIOL | WWM | REVIEW | Passed | |
07/02/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide energy code compliance calculations. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation. Reference: Sections 101.4 and 104.2, International Energy Conservation Code 2006. 2. Show the size, routing, and termination of the condensate drains. Reference: Section 307.2, IMC 2006 and Section 814.0, UPC 2006. |
07/06/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The applicable code for all commercial plumbing projects is the 2006 Uniform Plumbing Code with Local Amendments. 2. Provide overflow protection for the existing roof in which a new 12"x4" scupper is being installed. Reference: Section 1101.11, UPC 2006. 3. Provide hydraulic calculations to show that the proposed 4" diameter scuppers provide the capacity equivalent to the code-required minimum 6.25"x 4" scuppers. Reference: Sections 1101.11 and 1106.0, UPC 2006. 4. Provide overflow protection for the new roof. Reference: Section 1101.11, UPC 2006. |
07/06/2009 | ROBERT SHERRY | WATER | REVIEW | Denied | Reduced pressure backflow prevention assemblies are required at the water meter for multi-use commercial buildings. Reference: COT Ordinance 9976, http://www.tucsonaz.gov/water/docs/backflow-ord.pdf. |
07/13/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
07/14/2009 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
07/14/2009 | SUE REEVES | REJECT SHELF | Completed |