Review Date Reviewer's Name Type of Review Description Status Comments
06/12/2009 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 6-15-09
Activity: T09CM01245
Address: 10930 E. Escalante Rd.
Applicant: Charlie Dente

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Provide two copies of the corrected set of drawings (no clouds or revision numbers please) along with a set of the first submission (cloud corrections on this set please). All corrections and revisions shall be made on original tracings or finished reproducible set. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.

STRUCTURAL PLANS:
2. Specify the design criteria for exterior balconies (60 psf) Table R301.5.

SECTIONS - DETAILS:
3. Specify the design limit for the stair treads and risers (min. tread depth: 10"; max. riser height: 7 ¾") R311, R312.

PLUMBING PLAN:
4. Size the gas supply piping for the connected demand. Minimum 1¼" required to the first branch and minimum 1" branch lines to the furnaces, UPC 1217.0 Table 12-8.

MECHANICAL PLAN:
5. Combustion air openings into the garage are prohibited, R309.1.1.

ELECTRICAL PLAN:
6. Show the location of the service panel with a 30"W x 36"D clear working space, E3305.2, E3501.6.2.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review