Permit Number: T09CM01211
Parcel: 10602278D

Address:
211 W KING RD

Review Status: Completed

Review Details: SITE

Permit Number - T09CM01211
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/14/2009 DAVE MANN FIRE REVIEW Denied Fire Department access inadequate. Too far from King Rd., drive too narrow and not paved, no turnaround for fire trucks.
Please provide documentation of approved fire sprinkler system, or provide fire department access and fire alarm system. Also, please show existing hydrant location, with dimensions to property lines.
05/14/2009 RBROWN1 ADA REVIEW Passed NOT A COT OWNED/OPERATED PROPERTY
05/14/2009 RONALD BROWN ZONING HC SITE REVIEW Denied 1. Note 5 refers to all private property sidewalks to comply with IBC 1106 and ICC 117.1, Section 502. Both these code references are for parking and loading zones and have nothing to do with accessible route slope requirements.
2. Looks like a fire place jutting into new accessible route at North elevation of block 3 reducing the accessible route to somethingh less than 4' wide. Please confirm and note dimension on plan.
05/20/2009 STEVE SHIELDS ZONING REVIEW Approved
05/22/2009 PAUL MACHADO ENGINEERING REVIEW Denied To: Geoff Harris DATE: May 27, 2009
5405 E Placita Hayuco
Tucson, Arizona 85718

Subject: Assisted Living Parking, 211 W. King Road
Site plan T09CM001211 (First Review)
T13S, R13E, Section 25

RESUBMITTAL REQUIRED: Site Plan.

The Site Plan (SP) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Site Plan:

1. Please include a response letter to the comments along with the corrected copies of the SP.
2. Per the zoning decision, this site will be reviewed for full code compliance.
3. Min. paving material shall be double shot chip seal per the L.U.C.
4. Edit many of the general notes and omit any information not pertaining to this project.
5. As per the Federal ADA requirements, all wheel chair ramps shall have the truncated domes instead of the standard grooves that are shown on COT SD 207. Aside from the Truncated Domes, all wheel chair ramps shall be constructed in accordance with COT SD 207.
6. Show all points of egress and ingress including locations and width of driveways and parking area access lanes (P.A.A.L.) per D.S. 2-02.2.1.11.
7. Please label all vehicular, bicycle, pedestrian, and handicapped circulation clearly identified per D.S. 2-02.2.1.12.
8. Fully dimensioned loading space(s) and maneuvering area(s) per D.S. 2-02.2.1.14.
9. Please provide Drainage patterns and finished grades per D.S. 2-02.2.1.16.
10. Show Site plan number (T09CM01211) on all sheets per D.S. 2-02.2.1.29.
11. Show refuse container location, size, and access thereto fully dimensioned per D.S. 2-02.2.1.32 and D.S. 6-01.0.
12. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information.
13. Please show a typical cross section of the P.A.A.L. or call out the percentage of slopes. Call out the GB at the D/W, if applicable.
14. The Site plan may be titled as the "Site/Grading plan" so that the general notes may be kept.


If you have any questions, I can be reached at 837-4932 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4932 office
(520) 879-8010 fax
C:/211 W. King Rd_SITE
06/02/2009 PETER MCLAUGHLIN NPPO REVIEW Denied Submit NPPO plan or application for exception. Include acceptable documentation, which clearly indicates that the project will not impact Protected Native Plants. Such documentation includes photographs of the site taken from all sides of the property per DS 2-15.2.0.C.
06/02/2009 PETER MCLAUGHLIN LANDSCAPE REVIEW Denied 1. Indicate required 5-foot masonry wall for screening of the parking lot from adjacent residential and office-zoned properties. LUC Table 3.7.2-I

2. Within a vehicular use area, one (1) canopy tree is required for each ten (10) motor vehicle parking spaces or fraction thereof. The canopy trees must be evenly distributed throughout the vehicular use area and every parking space shall be located within forty (40) feet of the trunk of a canopy tree (as measured from the center of the tree trunk). LUC 3.7.2.3.A.1.a

3. An unpaved planting area, which is a minimum of thirty-four (34) square feet in area and four (4) feet in width, must be provided for each canopy tree. 3.7.2.3.A.1.c

4. The site plan must be accompanied by a landscape plan with information specified in Development Standard 2-07.0. The site plan and landscape plan must show identical site layout to avoid conflict between the two plans. The review will continue when documents are included with re-submittal.

5. Landscape plan shall include irrigation specification design and layout per DS 2-06.5.4.A & DS 2-06.5.4.B including source of irrigation, sleeves for driveways and sidewalks, locations of valves, low-flow bubblers or drip irrigation.

6. Additional comments may apply upon submittal and review of a landscape plan.
06/03/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
06/05/2009 CPIERCE1 OUT TO CUSTOMER Completed
06/05/2009 SUE REEVES REJECT SHELF Completed